Standby Power Equipment Data

Admalite Central Battery Systems

Unique Design & Easy Access

Central Battery Design

Attractive Finish & Easy Maintenance

• UNIQUE ENCLOSURE DESIGN • LOW MAINTENANCE
• SEGREGATED BATTERY • WIDE RANGE OF BATTERY OPTIONS
• RECESSED CONTROLS • MAINTAINED/NON-MAINTAINED UNITS
• RELIABLE CIRCUITRY • AC/DC and DC/DC UNITS AVAILABLE

Description

A central battery system consists of a bank of cells, either Lead Acid or Nickel Cadmium, with an automatic charger, changeover contactor and external luminaires. ADMALITE Central Battery Units are manufactured to the highest standards using quality components to provide long and trouble free service. Our cubicles are of a unique design and allow unequalled access for both the installer and the maintenance engineer. All cubicles are made from substantial gauge sheet steel, folded and welded before being primed and coated with a quality paint finish. Battery and charger have separate compartments and access to both is via lockable covers. The charging chassis is removable in case of major modification.

General Schematic Diagrams

Central Battery Up Tp 5 Amps

Maintained System (Charge Rate up to 5 Amps)

Central Battery Over 5 Amps

Maintained System (Charge Rate above 5 Amps)

Non-Maintained Central Battery Diagram

Non-Maintained System (Charge Rate up to 5 Amps)

Non-Maintained Central Battery Diagram

Non-Maintained System (Charge Rate above 5 Amps)

Input Voltage

220/240v 50Hz Single Phase, or 380/415v 50Hz Three Phase with failure detection relays fitted.

Charger

Thyristor controlled constant voltage type with electronic current limit and optional boost facility. Protected against short circuit, low battery voltage and reverse battery connection.

Recharge Time

Chargers rated to replace 90% of discharged capacity within 12 hours and full recharge within 24 hours.

Minimum Battery Voltage

The battery voltage at the end of a rated discharge shall not be les than 85% of the nominal system voltage as defined in BS5266.

Fuses

Industrial H.R.C. complying with the general requirements of BS88 Part 2 : 1975.

Contactors

To the relevant requirements of BS5424 as standard but BS764 types available on request.

Transformers

Double wound with either Split Bobbin or Earth Screen and complying generally with the requirements of BS171.

Indicators

Mains Healthy Neon
Charge Fail L.E.D.
Charge Ammeter
Battery Voltmeter
Others on request.

Cabinets

Fabricated from a minimum of 1.6mm mild steel, folded and welded for strength and rigidity. Metalwork is finished in stove enamel powder paint RAL7032 grey. The cabinets are of a unique design affording unequalled access for installation and maintenance.

Dimensions

Cabinet Ref. Height Length Depth
1 1000 600 440
2 1250 800 540
3 1250 1000 640
4 BATTERY TBA TBA TBA
4 CHARGER TBA TBA TBA

Model Number

The model number contains abbreviations of all the major features of the unit.
Example:
50volt system with valve regulated sealed lead acid battery to operate in the maintained mode supporting a load of 840 watts for 3 hours upon mains failure and complete with two double pole fused outputs.
Model Code: 50M3/840/AV/LV/2DB/S
Where:

50 Is the system nominal voltage
M3 Is the category signifying maintained 3 hour
840 Is the system rated wattage
AV Represents ammeter and voltmeter
LV Represents low voltage disconnect feature
2DB Indicates the number of outputs
S Represents the battery type

Battery Types

S Valve Regulated Lead Acid
F Flat Plate Lead Acid
P Plante Lead Acid
N Nickle Cadmium Alkaline
Also available on request Valve Regulated batteries fully to BS6290 Part 4 Ref B.

VALVE REGULATED LEAD ACID
(System Nominal 24 Volts)

DERATE MAXIMUM LOAD BY 20% FOR SPECIFIED DUTY THROUGHOUT BATTERY LIFE

Nominal No. Cells Max Watts
1hr
Max Watts
2hr
Max Watts
3hr
Battery Capacity A/hr Cabinet Ref No.
12 340 195 135 22 1
12 480 280 190 30 1
12 750 430 300 46 1
12 1050 610 420 68 1
12 1350 790 545 84 1
12 1550 925 635 98 1
12 1925 1120 780 120 1

VALVE REGULATED LEAD ACID
(System Nominal 50 Volts)

DERATE MAXIMUM LOAD BY 20% FOR SPECIFIED DUTY THROUGHOUT BATTERY LIFE

Nominal No. Cells Max Watts
1hr
Max Watts
2hr
Max Watts
3hr
Battery Capacity A/hr Cabinet Ref No.
24 680 390 270 22 1
24 960 560 380 30 1
24 1500 860 600 46 1
24 2100 1220 840 68 1
24 2700 1580 1090 84 2
24 3150 1850 1270 98 2
24 3850 2250 1560 120 2
24 4700 2800 1960 152 3

VALVE REGULATED LEAD ACID
(System Nominal 110 Volts)

DERATE MAXIMUM LOAD BY 20% FOR SPECIFIED DUTY THROUGHOUT BATTERY LIFE

Nominal No. Cells Max Watts
1hr
Max Watts
2hr
Max Watts
3hr
Battery Capacity A/hr Cabinet Ref No.
54 1500 890 610 22 2
54 2150 1250 870 30 2
54 3350 1950 1350 46 2
54 4800 2750 1900 68 3
54 6100 3550 2450 84 3
54 7150 4150 2850 98 4
54 8700 5050 3500 120 4

FLAT PLATE LEAD ACID
(System Nominal 24 Volts)

Nominal No. Cells Max Watts
1hr
Max Watts
2hr
Max Watts
3hr
Battery Capacity A/hr Cabinet Ref No.
12 260 160 115 18 1
12 535 320 235 36 1
12 800 480 355 54 1
12 1000 650 470 72 1
12 1325 800 590 90 2
12 1600 950 700 108 2
12 1900 1150 840 128 2

FLAT PLATE LEAD ACID
(System Nominal 50 Volts)

Nominal No. Cells Max Watts
1hr
Max Watts
2hr
Max Watts
3hr
Battery Capacity A/hr Cabinet Ref No.
24 520 320 230 18 1
24 1070 640 470 36 1
24 1600 950 700 54 3
24 2000 1300 940 72 3
24 2650 1600 1180 90 3
24 3200 1900 1400 108 4
24 3800 2300 1675 128 4
24 4750 2875 2100 160 4

FLAT PLATE LEAD ACID
(System Nominal 110 Volts)

Nominal No. Cells Max Watts
1hr
Max Watts
2hr
Max Watts
3hr
Battery Capacity A/hr Cabinet Ref No.
54 1170 720 530 18 3
54 2400 1450 1050 36 3
54 3600 2100 1600 54 2+2
54 4500 2900 2100 72 2+2
54 5900 3600 2650 90 2+3
54 7200 4300 3200 108 2+3
54 8500 5175 3750 128 2+3

HIGH PERFORMANCE PLANTE LEAD ACID
(System Nominal 24 Volts)

Nominal No. Cells Max Watts
1hr
Max Watts
2hr
Max Watts
3hr
Battery Capacity A/hr Cabinet Ref No.
12 200 130 95 15 1
12 400 260 190 30 1
12 600 400 285 45 3
12 800 520 380 60 3
12 1000 660 475 75 3
12 1440 480 640 100 3
12 1800 1050 790 125 4

HIGH PERFORMANCE PLANTE LEAD ACID
(System Nominal 50 Volts)

Nominal No. Cells Max Watts
1hr
Max Watts
2hr
Max Watts
3hr
Battery Capacity A/hr Cabinet Ref No.
24 400 260 190 15 2
24 800 520 380 30 3
24 1200 800 570 45 4
24 1600 1040 750 60 4
24 2000 1320 950 75 2+2
24 2875 1675 1275 100 2+2
24 3600 2100 1575 120 2+2
24 4300 2500 1900 150 2+2

HIGH PERFORMANCE PLANTE LEAD ACID
(System Nominal 110 Volts)

Nominal No. Cells Max Watts
1hr
Max Watts
2hr
Max Watts
3hr
Battery Capacity A/hr Cabinet Ref No.
54 970 575 430 15 4
54 1940 1170 855 30 2+2
54 2900 1800 1250 45 3+3
54 3975 2340 1700 60 3+3
54 4800 2950 2100 75 2+3+3
54 6450 3750 2850 100 2+3+3
54 8100 4725 3550 125 2+4+4

NICKEL CADMIUM ALKALINE
(System Nominal 24 Volts)

Nominal No. Cells Max Watts
1hr
Max Watts
2hr
Max Watts
3hr
Battery Capacity A/hr Cabinet Ref No.
20 170 115 80 11 1
20 300 208 150 20 1
20 400 275 200 26 1
20 510 350 250 33 1
20 680 460 330 44 1
20 920 630 450 61 1
20 1100 750 525 73 1

NICKEL CADMIUM ALKALINE
(System Nominal 50 Volts)

Nominal No. Cells Max Watts
1hr
Max Watts
2hr
Max Watts
3hr
Battery Capacity A/hr Cabinet Ref No.
40 340 230 160 11 1
40 600 410 300 20 1
40 800 550 400 26 1
40 1020 700 500 33 1
40 1360 920 660 44 2
40 1840 1260 900 61 2
40 2200 1500 1050 73 3
40 2550 1740 1240 83 3

NICKEL CADMIUM ALKALINE
(System Nominal 110 Volts)

Nominal No. Cells Max Watts
1hr
Max Watts
2hr
Max Watts
3hr
Battery Capacity A/hr Cabinet Ref No.
90 750 520 360 11 3
90 1375 950 650 20 3
90 1850 1250 900 26 3
90 2300 1575 1100 33 3
90 3050 2070 1500 44 2+2
90 4200 2825 2050 61 2+2
90 5000 3375 2400 73 2+2

BATTERY TYPES

Valve Regulated Lead Acid
These are state of the art in sealed lead acid technology, using a design in which the acid is immobilised in a sponge-like material. The electrolyte remains there throughout the charge and discharge cycles. During the life of the battery there is minimal loss through gassing. Service life up to 10 years.

Flat Plate Lead Acid
Low antimony pasted plate cells in translucent plastic cases, which make it easy to check the electrolyte level. The cells have a very low internal resistance, which results in very good regulation, especially at higher rates of discharge. A large electrolyte reservoir enables greater periods between topping up. This type of cell has a reasonable neglect tolerance and is economically priced. Service life 12 to 15 years.

Plante Lead Acid
These are high performance cells, offering ultra reliable trouble free service when well maintained. The cell casings are clear plastic making it easy to see the electrolyte and the reservoir is large to limit the maintenance required. The cells retain 100% capacity throughout their life and give excellent performance at high or low levels of discharge. Service life up to 25 years.

Nickel Cadmium Alkaline
These cells are extremely robust and will tolerate arduous operating conditions and both electrical and mechanical abuse. The cells have translucent cases, which make it easy to check the electrolyte level. Deep discharge has no adverse effect on the cell capacity and they can be left in a discharged condition without damage, unlike lead acid cells. Service life up to 25 years.

OPTIONAL EXTRAS

BS BS764 Contactor
EF Earth Fault Monitor
ET Engineers Test Key
FA Fire Alarm Relay
LV Low Voltage Disconnect
NW Night Watchman's Switch
PF Phase Fail Relays
TM Time Switch
XD Double Pole Fused Outputs
  Others on Request

HEALTH AND SAFETY

When lead acid and nickel cadmium wet cells are being charged they give off a potentially explosive mixture of oxygen and hydrogen. Always ensure adequate ventilation when installing equipment in confined areas and display signs warning against smoking and naked flames. Remember the battery is electrically live at all times and cannot be isolated in the conventional sense, therefore precautions should be taken to restrict unauthorised access to battery rooms and cabinets.

MINI RANGE OF CBU'S

A range of wall mounting, maintained and non-maintained central battery units for smaller premises.

SPECIFICATION

Input 230volts 1 phase 50Hz.
Output 24volts.
Charger Constant voltage.
Indicators Mains healthy Neon and charge fail L.E.D.
Alarms Volt-free charge fail relay contacts.
Protection Anti-surge fuses to input, and charger. HRC fuses to output. Low Voltage Disconnect.
Battery Sealed lead acid 10 year nominal.
Enclosure Wall mounting with lockable hinged front door and top gland plate. Finished in polyester epoxy resin grey RAL-7032 textured.


BASIC
REF
1 HOUR
WATTS
3 HOUR
WATTS
CAB
REF
15/24 195 86 A
24/24 313 138 B
38/24 495 218 B
48/24 620 275 C
65/24 720 373 D

CABINET SIZES

Ref Height mm Width mm Depth mm
A 500 400 200
B 600 500 250
C 700 500 250
D 800 600 250

MODEL REFERENCE

The basic reference shown in the table above gives battery capacity and voltage, a model reference number will show the voltage, category, rated wattage, battery type suffix and idents for any optional extras fitted.
e.g. 24M3/275/S This is a standard 3 hour maintained unit rated at 275 watts.

Read about emergency central battery units.

Site Designed and Developed by First Internet Manchester web design